II.

PC320 Specifications:


Power Requirements:

12VDC or 18-24VDC Input, +/-10%

Supply Current:

13mA + Sensor Current + Backlight + 4-20mA Output

150mA Maximum Total Current

Backlight Current:

23mA when on

Internal Fuse:

315mA

Power Adaptor:

18VDC Universal Power Supply, 90-220VAC Input

AC Version only

Sensor Types/Units:

Level (Feet, Inches, Meters, Centimeters, Custom)

Temperature (ºF, ºC, Custom)

pH (ph, Custom)

Conductivity (uS, mS, Custom)

Dissolved Oxygen (%, mbar, ppm, mg/L, Custom)

ORP (mV, Custom)

Turbidity (NTU, Custom)

Wind Speed (MPH, KPH, Ft/Sec, M/Sec, Custom)

Wind Direction (º, Custom)

Humidity (%, Custom)

Solar Radiation (W/M², Custom)

Pressure (mbar, hPa, inHg, PSI, Pa, Custom)

Custom (Custom)

Output Relays:

4 Independent SPDT Relays

Contact Rating:

8A @ 250VAC, 5A @ 30VDC Resistive

Level Sensor Input:

2-Wire or 3-wire, 4-20mA, 0-5VDC, 0-1VDC

Output:

4-20mA Scalable

Display/Keypad:

16 Character x 2 Line Backlit LCD, 8-Button Tactile Keypad

Sensor Resolution:

7 Digit Maximum, Auto-Floating point

Accuracy:

Sensor Accuracy + 0.1% + 1 Digit

Dimensions:

7.1”W x 5.1”H x 1.4D (180mm x 130mm x 35mm)

Weight:

1 lb

Advertising