SPECIFICATIONS

Page 3

3”,4”, 6”, 8”, 10”

ANSI 150 lb. drilling

150 psi (10.3 bar) working pressure

10˚ to 130˚ F (-12˚ to 54˚ C)
-40˚ to 158˚ F (-40˚ to 70˚ C)
+/- 1% of reading for flow between 10% to 100% of max flow

+/- 2% of reading for flow from cutoff to 10% of max flow
Ductile cast iron, powder coated w/NSF61 listed epoxy powder

Welded steel, epoxy-coated

Noryl®
Dual durometer rubber
Diecast aluminum, powder-coated (non-IP68)

Ductile Cast Iron (IP68)

316 stainless steel

EPDM
Rate Total
5

8

Gallon/Minute, Liter/Minute, Liter/Second,

Gallon, Gallon x 1000, Liter, Liter x 1000, Mega Liter,

Cubic Feet/Minute, Cubic Meter/Hour,

Cubic Meters, Cubic Meter x 1000, Cubic Feet,

Million Gallon/Day, Mega Liter/Day

Cubic Feet x 1000

WMX101:

8-32 Vdc at 30 mA max, with auxiliary battery for continuous operation during power failures

NOTE: Using an unregulated power supply >18 Vdc may damage the meter due to AC line input voltage fluctuation
WMX104:

2 Lithium 3.6V “D” batteries, replaceable, 1 year life under continuous use.

WMX101:

Current sinking pulse, opto-isolated, 30 Vdc at 10 mA max

WMX104:

Pulse output available only with addition of post-factory output cable

High Frequency (default); 10 units/pulse; 100 units/pulse; 1000 units/pulse

3”

4”

6”

8”

10”

25.228

16.362

6.307

3.344 2.150

6.665

4.323

1.666

0.883 0.568

>20 microSiemens/cm
Hardware/software, conductivity-based
NEMA 4X Standard (IP68/NEMA 6P Option)

Pipe Sizes

Fittings

Pressure

Temperature Operating

Non-Operating

Accuracy

Materials

Body (3” Only)

Body (4”-10”)

Liner (3” Only)

Liner (4”-10”)

Electronics Housing

Electrodes

O-ring (3” Only)

Display

Digits

Units

Power

Pulse Output

Signal

Pulse Rates

High Frequency

Pulse/Gal

Pulse/Liter

Conductivity
Empty Pipe Detection
Environmental

SPECIFICATIONS*

*Specifications subject to change. Please consult our website for the most current data (www.seametrics.com).

FLOW RANGE (3” - 10”)

Meter

Size

3”

4”

6”

8”

10”

Gal/Min Liter/Sec Gal/Min Liter/Sec Gal/Min Liter/Sec Gal/Min Liter/Sec Gal/Min Liter/Sec

Minimum

7.5

.47

12

.75

32

2

60

3.8

95

6

Maximum

700

44.2

1,000

63

2,400

151.4

4,400

277.6

7,000

441.6

Advertising