Remote operation – Extron Electronics MSG0603 User Manual

Page 13

Advertising
background image

11

2002 - INLINE, INC.

MSC0603 OPERATION MANUAL - v1.0 5/7/02

Remote Operation

RS-232 Control


The MSC0603 RS-232/RS-422/RS-485 serial control port accepts serial commands from a
control system, computer serial port, or any other device capable of sending out serial ASCII
commands at compatible baud rates. A complete listing of RS-232/RS-422/RS-485 codes is
included below.

Communication Protocol:

8 data bits

1 stop bit

No parity check

9600 baud (factory default setting)

Protocol Structure


All commands sent to the unit must contain a leading character, the actual command, and an
ending character. The MSC0603 can accept multiple commands, storing them in a buffer. It
immediately executes each command in the order it was issued.

The MSC0603 recognizes [ and ] as leading and ending characters, also called Command
Codes. The factory default for the Command Code is [ ]. The Command code can be changed
via RS-232. Some sample command codes follow. For example:

This part of the command
string...

Represents:

[

The leading character

ADDRxx

The actual command.

]

The ending character

This command string...

Means:

[ADDRxx]

Assign an address to the unit, 01 to 98,
where xx = 01-98.