PS 124 12 VDC, 4 Amp Power Supply • Installation Manual

PS 124, cont’d

8

Output power — wiring the DC output connectors

The PS 124 can supply 12 VDC to multiple devices using

3.5 mm, 2-pole captive screw connectors. The combined current

draw of the connected devices must not exceed 4 amps.

N

To verify proper polarity before connection to a device,

plug in the power supply with no load and check the

output polarity with a voltmeter. Remove power before

continuing.

W

When verifying power supply polarity, the two

power cord wires must be kept separate while the
power supply is plugged in.

To connect products to the outputs of the PS 124:
1

.

Cut the DC output cord to the length required.

2

.

Strip the jacket of the conductor wire (figure 8).

SECTION A–A

Ridges

Smooth

Power Supply

Output Cord

A

A

+

Ridges

Smooth

2-Pole Orange
Captive Screw

Connector

(12V)

Tie

Wrap

3/16”

(5 mm) Max.

Figure 8 — Power connector wiring

N

The length of the exposed (stripped) copper wires is

important. The ideal length is 3/16" (5 mm). Longer

bare wires can short together. Shorter wires are not

as secure in the captive screw connectors and could be

pulled out.

Do not tin the stripped power supply leads. Tinned

wires are not as secure in the captive screw connectors

and could be pulled out.

3

.

Slide the leads into the supplied 2-pole captive screw plug

and secure using an Extron Tweeker or small screwdriver.

4

.

Use the supplied tie wrap to strap the power cord to the

extended tail of the connector.