Protocols Supported

The DMXR module supports the current DMX standard ANSI E1.11 DMX512-A and is backwards
compatible to USITT DMX512 (1990). Also supported is ANSI E1.20 RDM (Remote Device
Management).

Installation

Default Settings Table









Network Setup

• Use the pinout configuration on page 6 to connect to the lighting controller.
• Including the DMX512 source, a maximum of 32 Incitos per LAN is allowed. Consult factory

for applications requiring more than 32 Incitos per LAN. Note: One universe fed into an opto-
splitter creates multiple LANs. See Figure 2

• Using the appropriate category cable, daisy chain between luminaires as shown in Figure 2.

Note: No T-TAPS, STARS (except by an opto-splitter) or Ys allowed.

• A termination plug is included with each luminaire. Ensure the termination plug is installed into

the last luminaire in the daisy chain. If this component is not installed the luminaires will exhibit
erratic/intermittent behavior.

• Several fixtures may have the same address if desired for zoning.
• In 16-bit mode it is NOT advisable to have fixtures addresses overlap; they should either have

the same address or be two addresses apart.

• 1000 feet with no splices is the maximum distance to the furthest luminaire per segment .

CJ520003 Rev. F

©2012 Acuity Brands Lighting, Inc.

All Rights Reserved.

4 of 12

DMX Address

001

DMX Channel

1-DMX Slot (8-bit level)

RDM Personality

Linear Curve

Incito Driver

Logarithmic curve (Overall
fixture response will be
logarithmic)

Loss of DMX Signal Hold last level forever