Maintenance and troubleshooting, Problem cause correction – Liberty Pumps ProVore 380 User Manual

Page 10

Advertising
background image

©Copyright 2013 Liberty Pumps Inc. All rights reserved 10

Risk of electric shock. Always disconnect the pump from the power source before handling or making

adjustments.





Problem

Cause

Correction

Pump will not run.

Blown fuse or other interruption of

power; improper voltage.

Check that the unit is securely plugged in.

Have an electrician check all wiring for proper

connections and adequate voltage and

capacity.

Switch is unable to move to the

“turn on” position due to

interference with the side of basin

or other obstruction

Position the pump or switch so that it has

adequate clearance for free operation.

Insufficient liquid level.

Make sure the liquid level is allowed to rise

enough to activate switch(s).

Defective switch.

Remove and replace switch.

Pump will not turn

off.

Switch(s) unable to move to the

“turn off” position due to

interference with the side of basin

or other obstacle.

Position the pump or switch so that it has

adequate clearance for free operation.

Defective switch.

Remove and replace switch.

Pump runs or hums,

but does not pump.

Discharge is blocked or restricted.

Check the discharge line for foreign material,

including ice if the discharge line passes

through or into cold areas.

Check valve is stuck closed or

installed backwards.

Remove check valve(s) and examine for

freedom of operation and proper installation.

Gate or ball valve is closed.

Open gate or ball valve.

Total lift is beyond pump's

capability.

Try to route piping to a lower level. If not

possible, a larger pump may be required.

Consult the factory.

Pump impeller is jammed or volute

casing is plugged.

Remove the pump from the basin, remove

cutter and cutter plate clan the area around the

impeller, reassemble and reinstall. The center

screw uses a 6mm hex drive. The screw can

be heated to remove thread locking compound.

Pump runs

periodically when

fixtures are not in

use.

Check valve was not installed, is

stuck open or is leaking.

Remove check valve(s) and examine for

freedom of operation and proper installation.

Fixtures are leaking.

Repair fixtures as required to eliminate leakage.

Pump operates

noisily.

Foreign objects in the impeller

cavity.

Remove the pump from the basin, remove

cutter and cutter plate clan the area around the

impeller, reassemble and reinstall. The center

screw uses a 6mm hex drive. The screw can

be heated to remove thread locking compound.

Broken impeller.

Consult the factory for information regarding

replacement of impeller.

Worn bearings.

Return pump to the factory or authorized repair

station for repair.

Piping attachments to building are

too rigid.

Replace a portion of the discharge line with

rubber hose or connector.

6. Maintenance and Troubleshooting