Installation

© Gardner Denver Deutschland GmbH

15 / 36

610.44444.40.000

Fig. 5: Remove cover plate:
Unscrew screws


Insert the connecting cable:

Thread the connecting cable into the cord
grips on the side panel of the separator and
push it through the cable inlet into the interior
of the separator.

Route the connecting cable into the terminal
box of the installed unit via the cable entry
opening.

 In order to relieve strain, secure the

connecting cable as follows:

via the cable gland on the terminal box of
the installed unit

via the cord grips on the outside of the
separator

Tightening torques: see Chapter 3.1,
"Mechanical data", Section "Tightening
torques", Pg. 9.

Fig. 6: Strain relief:
Cord grips on the outside of the separator


Connection to drive-motor terminal box:

Carry out the connection and the arrangement of
the jumpers in accordance with the circuit
diagram in the terminal box.

Connect the protective conductor to the terminal
with the following symbol:


The electrical connection must be carried out as
follows:

 The electrical connection must be

permanently safe.

 There may be no protruding wire ends.

 Clearance between bare live parts and

between bare live parts and ground: ≥ 5.5 mm
[0.217"] (at a nominal voltage of UN ≤ 690 V).

 Tightening torques for terminal plate

connections:
see Chapter 3.1, "Mechanical data",
Section "Tightening torques", Pg. 9.

 Use suitable cable lugs.

 For terminals with clamping straps, the

conductors must be inserted so that
approximately the same clamping height
results on both sides of the bar.
Individual conductors must therefore be bent
into a U-shape or connected with a cable lug.

 All conductors under outer angled grounding

brackets must be bent into a "U" shape.