ABUS FU8380 Secvest 2WAY Wireless Seismic Detector User Manual

Page 21

Advertising
background image

21

On

Sensitivity

Connect jumper C. Note: When the detector
battery is almost empty, the LED flashes
continuously for calibration mode. In this
case, replace the battery.

1. Turn the potentiometer anti-clockwise to

the stop. The detector is now at the
lowest sensitivity level.

2. Tap the sensor with your hand. Tap it at

the strength where the sensor should
trigger an alarm.

The calibration mode LED flashes:

Once for a small vibration

Twice for a vibration that triggers an
alarm

Three times for a strong vibration

3. Adjust the potentiometer until the LED

flashes twice at every vibration in the
desired sensitivity range.

4. Remove jumper A if the sensor does not

register all vibrations in the desired
sensitivity range.

5. Remove jumper C when the sensor has

been set to the desired sensitivity. This
puts the detector into normal operating
mode.