48/24vdc power connection – Alpha Technologies Radium MiniBay User Manual

Page 28

Advertising
background image

28

044-001-C0-00, Rev. C

Fig. 2-5, Power Connections

2.0

DC Air Conditioner, continued

2.5 48/24VDC Power Connection

Allow 20 minutes for completion of procedure.
Tools required: Assorted wrenches and screwdrivers

1. Install circuit breaker mounting plate in a convenient location near the 48/24VDC source

(see Fig. 2-5 below). Leave circuit breaker IN THE OFF POSITION.

2. Connect black wire leading from circuit breaker to the 48/24VDC Bus.

. Connect the red wire to the ground/return bar.

The air conditioner can be positively or negatively grounded. The overcurrent protection

must be placed in the ‘Hot’ lead.

To Ground Return Bar

To Circuit Breaker

Circuit

Breaker