3 input feed, 4 alarms – Alpha Technologies 32-0-10A Fuse Panel User Manual

Page 13

Advertising
background image

A

RGUS

T

ECHNOLOGIES

32-0-10A

F

USE

P

ANEL

020-103-C0 R

EV

B

P

AGE

5 of 6

4.3 Input

Feed

Each input feed corresponds with position A or B on terminal block TB1 located at
the rear of the unit (see Figure 3 and schematic 020-103-05).

WARNING Ensure the correct polarity is used for all input cable

terminations.

The panel is equipped with a #10-32x½” pan head screw at each termination and on
the ground bar. Connect “hot” leads to the corresponding terminals and common
leads to the ground bar.

4.4 Alarms

All alarms provide jumper selectable Form A/B alarm contacts, which correspond
with terminal blocks located at the rear of the unit (see Figure 3).

All applicable alarms should be connected to the local alarm-sending unit from the
fuse panel. Terminal blocks can accommodate wire sizes 0.34 to 2.5 mm

2

(#22 to #14

AWG).

Figure 3–Rear view showing connections for input and alarms

ALARM
CONNECTIONS

INPUT FEED B

INPUT
RETURN A & B

INPUT FEED A