5 Maintenance

Although very little maintenance is required with Argus systems, routine checks and adjustments are
recommended to ensure optimum system performance. Qualified service personnel should do repairs.

The following table lists a few maintenance procedures for this system. These procedures should be performed at
least once a year.

WARNING: HIGH VOLTAGE AND SHOCK HAZARD.

Use extreme care when working inside the shelf while the system is energized.
Do not make contact with live components or parts.

Ensure redundant modules or batteries are used to eliminate the threat of service interruptions
while performing maintenance on the system’s alarms and control settings.

Procedure

Date Completed

Clean ventilation openings

Inspect all system connections (re-torque as necessary)

Inspect batteries
(consult battery manufacturer’s recommended procedure)

Verify alarm/control settings

Verify alarm relay operation

Table A–Sample maintenance log

5.1

Breaker/Fuse Block Replacement

WARNING
Use extreme caution and do not touch any connected equipment.

To gain access to the breakers (or fuse blocks), turn the two front panel latches counter-clockwise and tilt the
front panel forward and down.

Ensure the breaker/fuse block to be replaced is in the OFF position.

To remove the breaker/fuse block from the swaged bullet receptacles, grasp the block (finger to thumb) by the top
and bottom and gently pull (with even force) away from the panel.

Ensure new breakers/fuse blocks are of the same rating as the ones being replaced. Consult factory for up-to-
date ordering information.

Again, ensure that the new breaker/fuse block is in the OFF position before installing.