Specifications, General – Alpha Technologies Rear Access Bullet Breaker Panel, 19 User Manual

Page 5

Advertising
background image

Specifications for Argus’ Rear Access Bullet Breaker Panels

Argus Technologies Ltd.

020-671-B1 Rev B WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.

Page 1 of 2

General

Alarm:

Jumper selectable Form A (normally open) or Form B (normally closed) contacts


Input Termination (typical):

1 pair of 3/8” clearance holes on 1” centers for bus bar or wire lug;
See also connections drawing for termination list options


Load Termination (typical):

2x1/4”-20 lugs on 5/8” centers (1 per breaker) for up to #2AWG;
See also connections drawing for termination list options


Breaker Option:

AM-type mid-trip plug-in breaker, 5/16” bullet-style terminals;
No alarm jumper wires are required


Ampacity:

600A total for List 80 (single feed),
2x 600A for List 81 (dual feed);
Breakers available 5-100A 1-pole, 125-150A 2-pole, 175-250A 3-pole


020-671-20

Shelf Size:

133mm H x 534mm W x 182mm D
(5.25” H x 21” W x 7.15” D)
[dimensions do not include mounting brackets and fasteners]


Mounting: 23”

rack


020-675-20

Shelf Size:

133mm H x 432mm W x 182mm D
(5.25” H x 17” W x 7.15” D)
[dimensions do not include mounting brackets and fasteners]


Mounting: 19”

rack