System specifications, Output, Input – Alpha Technologies CXPS 48-1.8-i, 48V Pos Gnd User Manual

Page 4

Advertising
background image

Specifications for Argus’ CXPS 48-1.8-i 48Vdc Power System

Argus Technologies Ltd.

053-990-B1 Rev A WC

Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 1 of 3

Output

Voltage:

42 to 58Vdc within rated limits


Current:

System:

150A maximum @ nominal input
~96A @ 115Vac input

Rectifier Module:

37.5A maximum @ 48Vdc (nominal input)
~24A @ 48Vdc (115Vac input)


Power:

System:

7200W maximum @ nominal input
~4600W @ 115Vac input

Rectifier Module:

1800W maximum @ nominal input
~1150W @ 115Vac input (de-rated linearly to 900W @ 90Vac)


Heat Dissipation (per rectifier): <607 BTU per hour per rectifier module

Static Load Regulation:

Better than ±0.5% for any load change within rated limits


Dynamic Load Regulation:

Better than ±2% for 10% - 90% load step
(output shall recover to static limits within 10ms)


Static Line Regulation:

Better than ±0.1% for any change in input voltage within rated limits


Dynamic Line Regulation:

Better than ±1% for any change in input voltage within rated limits

(output voltage shall recover to static limits within 2ms)


Electrical Noise:

<32dBrnC (voice band)
<30mVrms 10kHz to 10MHz (wideband)
<150mVp-p 10kHz to 100MHz
<1.0mV (psophometric)


Acoustic Noise:

<60dBa @ 1m (3ft.) @ 30°C (86°F)


Input

Voltage:

Nominal:

208/240Vac

Operating:

176 to 312Vac

Extended (High):

312 to 320Vac (de-rated power factor)

Extended (Low):

90 to 176Vac (de-rated output power)


Frequency:

45 to 66Hz


Current:

8.5A @ 240Vac (11.5A maximum @ 176Vac)


Power Factor:

>0.99 at nominal conditions and 50-100% load


Efficiency:

>90% at nominal conditions and 50-100% load


Recommended Feeder Breaker

Single Phase:

15A, 120 or 240Vac, 2.5mm

2

(#14 AWG) per rectifier module


Advertising