Specifications for Argus’ CXCI Cordex Controller Integrated Model Continued

Argus Technologies Ltd.

707-492-B1 Rev B WC

Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 2 of 2

Hardware Specifications, CXCI

CPU: Coldfire

RAM: 8MB

Flash: 4MB

standard


Display:

4 digit LCD


Front Panel Controls:

Display pushbutton toggle switch for voltage (V) or current (A)
CXCI reset switch (soft reset button; hold for 3 seconds to reset IP)


LED’s:

System OK (Green)
Power System Minor Alarm (Yellow)
Power System Major Alarm / Controller Fail (Red)


Audio:

Built-in speaker for alarm and popup message tones


Dimensions:

88mm H x 26mm W x 280mm D
(3.5” H x 1” W x 11“ D)


Weight:

0.34 kg (0.75 lb.)


Mounting:

Integrated on Cordex 2RU series 19” and 23” shelves


Relay Outputs:

Four (4) Form C, 60Vdc 1A maximum


Digital Inputs:

Two (2), 0 to 60Vdc


Analog Inputs:

One (1) DC voltage, 0 to 60Vdc
One (1) DC current, ±50mV
Two (2) temperature, 0 to 20Vdc with power source


Communication Ports:

Ethernet RJ-45, Argus Modem DB-9, CAN [see shelf specifications]


Recommended Signal Wire Sizes (as per UL/CSA)

Wire Size Range:

0.14 to 1.50mm

2

(#26 to #16 AWG)


Temperature Range:

0 to 50°C
(32 to 122°F)



CAUTION – TO REDUCE RISK OF FIRE, USE ONLY 0.14mm

2

(#26 AWG) OR LARGER WIRE.