5.6.1 DC input to panel

The distribution center contains a bus bar input for hot and return connections. The power system is configured

with vertical bus bars for rectifier shelf integration purposes. The bus bar inputs are fixed for hot and return

placement.

Figure 9–Rear view of distribution panel

5.6.2 Distribution cabling

Refer to the guidelines supplied with the load equipment. Distribution cables are typically sized to provide a 0.5V

loop drop at full load as well as meeting ampacity requirements of the protection fuse or circuit breaker. Terminate

the distribution cables to the distribution center with ¼"–5/8"C lugs.

5.6.3 Breaker output (hot) connections

Connect the breaker output (hot) cables before connecting the breaker return (ground) cables. Secure the two

hole lugs to the ¼" studs (on 5/8" centers) using the hardware supplied with the distribution center. Run the

cables directly out of the rear of the distribution center. Refer to Figure 10.

5.6.4 Breaker return (ground) connections

Connect the breaker return (ground) cables o the distribution center ground bar. Secure the two hole lugs to the

¼" studs (on 5/8" centers) using the hardware supplied with the distribution center. Run the cables directly out of

the rear of the distribution center above the breaker output (hot) cables.

5.6.5 Battery breaker connections

Connect the battery breaker (hot) connections first using the same guidelines as the load cable installation.

Connect the battery ground cables using the same guidelines as the load return cables. The cables should run

directly out of the rear of the distribution center above the breaker output (hot) cables.

Figure 10–Battery, load, and return connection locations

Distribution

center input

(hot) bar

Load breaker (hot) connection

System return (ground) bar

Battery (hot)

Distribution

center input

(return) bar