Page 26 of 33

6 System startup

After completing the system installation and power system wiring, perform the following:

6.1 Check system connections

Ensure that the AC input is switched off, the battery breaker is off, and all power modules are removed from

the shelf.

Triple-check the polarity of all the connections.

6.2 Verify AC input and power up rectifier shelf

Install one rectifier module.

Verify that the AC input voltage is correct and switch on the corresponding feeder breaker.

The controller OK LED light should illuminate continuously after a preset start delay.

Using the controller, test the functionality of all module alarms and controls.

6.3 Check battery polarity and connect the batteries

Verify the polarity of all the batteries with a voltmeter to ensure that no cells or batteries are reversed.

Switch on the appropriate battery breaker.

Install the remaining power modules.

Use a web browser to access the adjustments menu of the controller. Set the float and equalize the voltage to

the levels specified by the battery manufacturer.

Using the controller, test the functionality of various module alarms and controls. In addition, perform a load

test with the system using a resistive load box if needed.

Enable the temperature compensation (Temp Comp) feature on the Batteries menu. Program the slope

setting and the upper and lower breakpoints according to the specific battery requirements.

6.3.1 Controller alarm Configuration for nominal 120 Vac operation

The default setting for the low AC input alarm is 180 Vac. For a nominal 120 Vac input, reset this value to

100 Vac.
To reconfigure this alarm parameter, go to “Alarms” and then “Configure Alarms”. Under “Alarm Configuration,”

select “Voltage Alarms.” Select and modify the activation value for “AC Mains Low” to 100 Vac. Submit the

changes to save the new configuration.