6.10 Alarm and Signal Wiring Connections for CXCM

For terminal block connections, the recommended wire sizes are 0.75 to 0.14mm

2

(#18 to #26 AWG) for the

temperature range of 0 to 50 deg. C (as per UL/CSA).

For insulation displacement receptacles, the recommended wire size is 0.75mm

2

(#18 AWG).

CAUTION: to reduce risk of fire, use only 0.129mm

2

(#26 AWG) or larger wire.

Terminal

Description

Signal Type

Range

Alarm Outputs –

Can be configured to de-energize on alarm (DOA) or energize on alarm (EOA).

#2-21,22(common)

K2, LVD2

NC/COM/NO (JP2)

60Vdc / 1A

#3-19,20(common)

K3, LVD3

NC/COM/NO (JP3)

60Vdc / 1A

#4-17,18(common)

K4, System Minor

NC/COM/NO (JP4)

60Vdc / 1A

#5-15,16(common)

K5, System Major

NC/COM/NO (JP5)

60Vdc / 1A

#6-13,14(common)

K6, AC Mains Hi-Low

NC/COM/NO (JP6)

60Vdc / 1A

#7-11,12(common)

K7, Not assigned

NC/COM/NO (JP7)

60Vdc / 1A

#8-9,10(common)

K8, Not assigned

NC/COM/NO (JP8)

60Vdc / 1A

#0-25,24,23

K0, System Fail Output*

NC/COM/NO

60Vdc / 1A

Digital Inputs –

See Table B for definitions of logic and system

P5-1,2

D1, Distribution Fuse (Alarm)

Pos (+) or Neg (-)

0—60Vdc

P5-3, P6-1

D2, Distribution CB (Alarm)

Pos (+) or Neg (-)

0—60Vdc

P6-2,3

D3, Battery CB (Alarm)

Pos (+) or Neg (-)

0—60Vdc

Analog Inputs and System Signals

E1

Battery -48V**

Neg (-)

20—60Vdc

J3

Ethernet port

N/A

N/A

P1-2,1

K1, LVD1

Pos (+) / Neg (-)

0—60Vdc / 1A

P7-2,1

V1, Load Voltage

Pos (+) / Neg (-)

0—100Vdc

P8-2,1

I1, Load Current

Pos (+) / Neg (-)

±50mV

for List 120, add the following:

1-2

T1 (GP1), Temp Probe 1

Pos (+) / Neg (-)

0—20Vdc

, with power source

3-4

T2 (GP2), Temp Probe 2

Pos (+) / Neg (-)

0—20Vdc

, with power source

5-6

GP3, General Input 3

Pos (+) / Neg (-)

Not used

7-8

GP4, General Input 4

Pos (+) / Neg (-)

±60V,

bi-polar voltage

for List 124, consult the factory to add the following:

1-2

V3 (GP1), Voltage Input 3

Pos (+) / Neg (-)

0—60Vdc

3-4

V4 (GP2), Voltage Input 4

Pos (+) / Neg (-)

0—60Vdc

5-6

V5 (GP3), Voltage Input 5

Pos (+) / Neg (-)

0—60Vdc

7-8

T1 (GP4), General Input 4

Pos (+) / Neg (-)

0—20Vdc

, with power source

Table B–Signal wiring connections for CXCM

*

System Fail output relay is fail-safe and will de-energize during an alarm condition.

**

Battery –48V: connect to battery only when using a battery disconnect device

NOTE: To aid the user with installation, frequent reference is made to drawings located at the rear of this manual.

Custom configurations may be detailed within the Apha power system documentation package.