SIZE

DWG NO.

TYPE

B

SHEET

TITLE

ISSUE

DATE

OF

TOLERANCES

SCALE

APPROVED

CHECKED

DRAWN

DESIGN

MATERIAL

FINISH

FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.

ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED

THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF

REVISIONS

LTR

DESCRIPTION

APPD

DATE

REV

X.X

0.04"

X.XX

0.02"

X.XXX

0.01"

[X]

1mm

[X.X]

0.5mm

[X.XX]

0.25mm

030-706-08

CUSTOMER CONNECTION,

6 MOD OR 5 MOD w CXC SUP.

48-1kW CXRC 19/23" MNT SHELF

PER P.O. and

Doc. 070-024-83

1 3

DGW

DGW

2004/05

2004/05

D2

c 2004 ARGUS TECHNOLOGIES

O

C

DIMENSIONS ARE IN INCHES WITH METRIC [mm] IN BRACKETS: INCHES [mm]

J.K.

2004/05

W.E.S.

2004/05

NTS

REV BY

B SPECIFIED RECTIFIERS FED BY TB1 & TB2

M.P. 2005/11

C UPDATED AC I/P TERMINAL BLOCK

FROM LINE 2 TO L2/N

M.P. 2007/09

WES

TB1

L1

L2/N

#6-32 SCREWS

TYPICAL AC INPUT TERMNINAL BLOCK

( TB1 SHOWN )

TB1 FEEDS RECTIFIERS 1, 3, 5
TB2 FEEDS RECTIFIERS 2, 4

C

J3

P1

P1

J3

E2 - COMMON (+)

E1 - LIVE (-)

AC INPUT KNOCKOUT PLATE
(REVERSIBLE)

AC

INPUTS

1.125" KO
ACCEPTS 3/4" FITTING/CONDUIT

.875" KO
ACCEPTS 1/2" FITTING/CONDUIT

#1/4-20 CHASSIS GROUND

CXCM BACKPLANE
(707-340-20)

DC

OUTPUT

USES 1/4-20 x 5/8" OUTPUT LUGS

TIGHTEN TO 8 FT-LB

TB1

TB2

LIST 0,6 : 5 MODULE WITH CXC CONTROLLER

CAN TERMINATED

JUMPER SETTING FOR P1

1. GND
2. CAN H
3. NOT CONNECTED
4. CAN L
5. NOT CONNECTED
6. NOT CONNECTED

CAN OUT RJ12 OFFSET

PIN OUT (J3)