Installation, Continued, 1 installation in an xm series 2 power supply – Alpha Technologies USM2.5 Status Monitoring Module User Manual

Page 10

Advertising
background image

1. Installation

10

018-041-C0-003 Rev. C

11. Using the two captive screws just behind the face plate, secure the transponder

to the inverter module.

12. Verify that the 10-position jumper on the transponder is set to the correct

battery pack voltage.

13. Verify that the 8-position DIP Switch on the USM2.5 is set correctly. Refer to the USM2.5

operators manual (Alpha p/n 704-683-B0).

14. Set the inverter module onto the guides, and slide it 1 or 2 inches into the power supply.

15. Reconnect the ribbon cable to the inverter module, and latch the two retaining

clips over the ribbon cable plug.

16. Slide the inverter module fully into the power supply, and tighten the thumb

screws. Set the BATTERY BREAKER to the ON position.

17. Verify after 10-30 seconds, the Smart Display on the power supply reads

'OPERATION NORMAL'.

18. Download Alarm Profile from CheetahNet to initiate appropriate mode of operation.

19. Verify that, after approx. 1 minute, the 'CPU' LED on the front of the transponder

is blinking, if not, press the RESET button behind the hole next to the LEDs
(see fig. 1-2).

1.1

Installation in an XM Series 2 Power Supply,

continued

Figure 1-1 Transponder Installed

10(b).

For a USM2.5 with two ribbon cable sockets (J2, J3):
Attach one end of the 3-position ribbon cable to the connector (JP2) at the top of the
transponder, and the other two connectors to the USM2.5 (J2, J3). (fig. D)

8 Position DIP

Switch

10 Position

Jumper

Captive

screw

Captive

screw

Advertising