2. Specifications

22

018-041-C0-003 Rev. C

2.1

Channel Parameters

Table 2-1 Channel Parameters

Hi State

Lo State

Channel
Description

Parameter name

Units

Maj Low

Min Low

Min Hi

Maj Hi

Note

Analog Inputs

Internal Temperature

(C)

0

10

50

60

Analog Inputs

External
Temperature

(C)

0

10

50

60

3

Analog Inputs

AC Output Current 1

(AMPS)

0.5

2

25

25.5

Analog Inputs

AC Output Current 2

(AMPS)

0.5

2

25

25.5

Analog Inputs

Battery Voltage #1

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #2

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #3

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #4

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #5

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #6

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #7

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #8

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #9

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #10

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #11

(VDC)

10

11

14.4

14.8

Analog Inputs

Battery Voltage #12

(VDC)

10

11

14.4

14.8

Analog Inputs

AC Output Voltage

(VAC)

50

55

95

98

Analog Inputs

AC Input Voltage

(VAC)

95

100

125

128

2

Digital input

Standby Mode

Normal

Standby

Digital input

Tamper Switch

Open

Closed

Digital input

Output Fail Alarm

Normal

Alarm

Digital input

General Alarm

Normal

Alarm

1

Digital input

APU Test Fail

Alarm

Normal

1

Digital input

Engine Status

OFF

ON

1

Digital input

APU Fail / ECM

Alarm

Normal

1

Digital input

APU Response

Alarm

Normal

1

Digital input

Gas Hazard Alarm

Alarm

Normal

1

Digital input

APU Engine Alarm

Alarm

Normal

1

Digital input

Generator Enclosure

Open

Closed

1

Digital input

Generator Tamper

Closed

Open

1

Digital output

Standby ON / OFF

OFF

ON

Digital output

Equalize ON / OFF

OFF

ON

Digital output

Engine ON / OFF

OFF

ON

Note 1 - Generator
Note 2 - AC Input 120 VAC Models
Note 3 - External Temperature

Analog Inputs

AC Input Voltage

(VAC)

200

210

245

255

4

Analog Inputs

Generator Battery

(VDC)

10

11

14.4

14.8

Note 4 - AC Input 240 VAC Models