Troubleshooting – Alpha Technologies USM2.5 Status Monitoring Module User Manual

Page 23

Advertising
background image

23

018-041-C0-003 Rev. C

3. Troubleshooting

3.1

Important Troubleshooting Notes

Always troubleshoot communication problems before working on battery-related and/or generator-
related problems. The embedded transponder runs off of the power supply’s USM2.5 logic voltages,
and does not require the sensing cables (from the batteries or the generator) to communicate.

1.

USM2.5 Switch Set-up: The 8 position “DIP” switch on the USM2.5 board must be set correctly.
See the complete chart in the USM2.5 Status Monitor Operator’s and Technical Manual P/N
704-683-B0-xxx. Note that SW1-4 (the fourth switch from the front) must be turned ON when
using an internal Acterna transponder.

USM2.5 Switch Settings for Embedded Acterna Transponders

2.

Transponder Address: The transponder address is the five (5) digit number printed on the sticker
on the FRONT of the Embedded Transponder Assembly, above the “F” connector. The address
is not the printed circuit board serial number (typically in the format of 1B followed by six
numbers) from the sticker on the PCB itself.
The address can be verified from the SOC (Sys-
tems Operation Center).

3.

Transponder Driver: The correct Acterna device driver must be downloaded from the HEC to the
transponder. The following is Acterna’s list of device drivers for embedded (internal) transponders
in Alpha Technologies XM2 power supplies, as of 17 October 2002.

XM2 Models

all XM2 -610 & -615; all XM2-910 &

-915; XM2-1350 @ 75VAC or 90VAC

XM2-1350 @ 60VAC

XM2-1350-48 @ 75VAC or 90VAC

XM2-1350-48 @ 60VAC; all XM2-922

SW

1

SW

2

SW

3

SW

4

SW

5

SW

6

SW

7

SW

8

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

ON

off

off

off

off

off

off

off

off

off

off

off

off

off

off

off

off

off

off

Acterna

Battery

Input / Utility Power

Driver #

Voltage

Battery Monitoring

Voltage

Generator

Supply

8028

36VDC

4 battery strings max

120VAC

none

single

8029

36VDC

3 battery strings max

120VAC

with generator

single

8030

48VDC

3 battery strings max

120VAC

none

single

8031

48VDC

2 battery strings max

120VAC

with generator

single

8033

36VDC

4 battery strings max

240VAC

none

single

8034

36VDC

3 battery strings max

240VAC

with generator

single

8035

48VDC

3 battery strings max

240VAC

none

single

8036

48VDC

2 battery strings max

240VAC

with generator

single

8037

48VDC

1 battery strings max

240VAC

with generator

dual