2. Installation

30

031-165-C0-001 Rev. A

2.6

Battery Installation,

continued

Battery Post

3/8" Spacer

Fuse

Flat Washer

Lock Washer

Nut

Battery Cable to Next

Battery

3.6.3

Battery Terminal Connections

The accompanying drawings are for

illustrative purposes only. Various types of batteries

with different mounting styles and hardware may be shipped with the system. ALWAYS
refer to the battery manufacturers’ specifications for correct mounting hardware and torque
requirements. During maintenance procedures, refer to the manufacturers' specifications
for the maintenance torque requirements.

For AlphaCell batteries, use 65 Inch-Pounds upon installation, torque to 50 Inch-Pounds
during maintenance.

A corrosion inhibitor should be used on all bare metal connections and crimps

Mounting hardware requirements may vary with battery manufacturers. Use only the
hardware recommended by your particular battery manufacturer.