Preface

8

031-165-C0-001 Rev. A

Battery Safety Notes

Chemical Hazards

Any gelled or liquid emissions from a Valve-Regulated Lead-Acid (VRLA) battery is
electrolyte which contains dilute sulfuric acid which is harmful to the skin and eyes; is
electrically conductive; and is corrosive.

If electrolyte contacts the skin, wash immediately and thoroughly with water.

If electrolyte enters the eyes, wash thoroughly for 10 minutes with clean water or a
special neutralizing eye wash solution and seek immediate medical attention.

Neutralize any spilled electrolyte with the special solutions contained in a “spill kit” or with
a solution of 1 lb. Bicarbonate of soda to 1 gal. of water. Report accident, and seek
medical attention if necessary.

Fire, Explosion, and Heat hazards

Lead acid batteries can contain an explosive mixture of hydrogen gas which can vent
under overcharging conditions.

Do not smoke or introduce sparks in the vicinity of the battery.

Prior to handling the batteries, touch a grounded metal object, such as the rack, to
dissipate any static charge that may have developed in your body.

Do not charge batteries in a sealed container. The individual batteries should have 0.5
inches of space between them to allow for convection cooling. If contained, assure the
container or cabinet and room have adequate ventilation to prevent an accumulation of
potentially dangerous gas.