Sx s, Eries, Pecifications – Atec Elgar-501b User Manual

Page 6: Specifications, Single-phase output power, Dual-phase output power, Three-phase output power, Model power output input physical comments

Advertising
background image

Elgar

1.800.733.5427

858.450.0085

Fax 858.458.0267

9250 Brown Deer Road, San Diego, CA 92121

www.elgar.com

email: [email protected]

25

SX S

ERIES

S

PECIFICATIONS

SPECIFICATIONS

OUTPUT
Voltage Range:
0-65/130/260 VAC (varies
per model). Specific output range is
selected by jumper change on rear panel.
Consult Elgar for other voltage ranges.

Rated Power Voltage Range: Full rated
VA from 55-65 VAC, 110-130 VAC, or
220-260 VAC over a ±10% input and rated
PF range. Continuous duty at 150% of
rated capacity at 55°C*

Load Power Factor: Unity to ±0.7 PF to
rated VA with an output voltage
adjustment range of 80-100% of full scale*

Frequency Range: 45 Hz to 1kHz

Total Harmonic Distortion:
0.5% from 45 Hz to 1 kHz with linear load
1.0% from 45 Hz to 75 Hz with pulsed load
4.0% from 75 Hz to 450 Hz with pulsed load

Load Regulation: ±1% from 45 Hz to
450 Hz with pulsed load or from 45 Hz to
1 kHz with linear load

Line Regulation: ±0.25% at rated load for
a ±10% input change at full scale output
voltage

Response Time: <2 ms

AC Noise Level: 70 dB below full output
voltage with input grounded

INPUT
Voltage:
115/208/230 VAC, ±10% (208 VAC
not available on 501 SX.) User selectable
(See model description on page 23)

Frequency: 47 to 63 Hz (400 Hz option,
special order)

Efficiency: Up to 45%

GENERAL
Operating Temperature Range:
0° to
+55°C

Operating Humidity Range: Up to 95%
non-condensing

Metering: 0 to 300 VAC output voltmeter,
±3% accuracy

Controls: Input power switch/circuit
breaker and pilot light. Full range, 10-turn
output voltage control potentiometer

* See power derating curve on page 23.

Single-Phase Output Power

Model

Power

Output

Input

Physical

Comments

Total VA

Vol. Range Max Current

Frequency Range

Voltage and Nominal/Max

Height and Depth

Weight

(RMS)L-N

(RMS)

1

(Hz)

Phase

(kVA)

2

(in/mm)

(lbs/kg)

501 SX-X4

500

0-65

11.5/36

45 to 1k

115 or 230,

1.5/2.2

5.25/133

H

80/36

Net

0-130

5.8/18

21/533 D

88/40

Ship

0-260 2.9/9

1001 SX-X4

1000

0-65

23.1/72

45 to 1k

115, 208 or

3.0/4.2

7.00/178

H

130/59

Net

0-130 11.5/36

230,

21/533

D

140/64

Ship

0-260

5.8/18

1751 SX-X4

1750

0-65

40.4/120

45 to 1k

115,108 or

5.2/7.5

12.25/311

H

195/89

Net

&

0-130

20.2/60

230, 1ø

21/533

D

205/93

Ship

1751 SXE-2X

0-260

10.1/30

1751 SXE-24 only

Dual-Phase Output Power

1000 SX-2-X4

1000

0-65

11.5/36

45 to 1k

115 or 230,

3.0/4.4

10.50/267

H

160/73

Net

2 ea 501 SX in 2ø 90°, 1ea 400 SR,

0-130

5.8/18

21/533

D

176/80

Ship

1ea signal cable

0-260

2.9/9

2000 SX-2-X4

2000

0-65

23.1/72

45 to 1k

115,208 or

6.0/8.4

14/356

H

260/118

Net

2ea 1001 SX in 2ø 90°, 1ea 400 SR,

0-130 11.5/36

230,

21/533

D

280/127

Ship

1ea signal cable

0-260

5.8/18

3500 SX-2-X4

3500

0-65

40.4/120

45 to 1k

115, 208 or

10.5/15.0

24.50/622

H

390/177

Net

2 ea 1751 SX or 1751 SXE in 2ø 90°,

&

0-130

20.2/60

230, 1ø

21/533 D

410/186

Ship

1 ea 400 SR, 1 ea signal cable

3500 SXE-2-2X

0-260

10.1/30

3500 SXE-2-24 only

Three-Phase Output Power

1500 SX-3-X4

1500

0-65

11.5/36

45 to 1k

115 or 230,

4.5/6.6

15.75/400

H

240/109

Net

3 ea 501 SX (4 wire Y),

0-130

5.8/18

1ø or 3ø

21/533

D

264/120

Ship

2 ea 400 SR, 1 ea signal cable

0-260

2.9/9

3000 SX-3-X4

3000

0-65

23.1/72

45 to 1k

115, 208 or

9.0/12.6

21/533

H

390/177

Net

3 ea 1001 SX (4 wire Y)

0-130

11.5/36

230, 1ø or 3ø

21/533

D

420/191

Ship

2 ea 400 SR, 1 ea signal cable

0-260

5.8/18

5250 SX-3-X4

5250

0-65

40.4/120

45 to 1k

115, 208 or

15.7/22.5

36.75/933

H

585/266

Net

3 ea 1751 SX or 1751 SXE (4 wire Y),

&

0-130

20.2/60

230, 1ø or 3ø

21/533 D

615/280

Ship

2 ea 400 SR, 1ea signal cable

5250 SXE-3-2X

0-260

10.1/30

5250 SXE-3-24 only

1

All SX models specified are at 150% of nominal output current into a linear resistive load.

2

Maximum volt/amps under worst case conditions of load and input line at 150% capacity.

Advertising