3060-MS

© 2012 Pacific Power Source, Inc. Specifications subject to change without notice.

DS#43060MS122012

Page 3 of 4

POWER 62.5kVA/50kW for each 3060-MS

VOLTAGE

(Nominal)

Direct Coupled:

0-120/208 V, 3-phase

External

CURRENT RMS 175 A

RMS

/Phase continuous

Pf < 0.8=175A

RMS

/Phase

Pf 1.0=140A

RMS

/Phase

OVERLOAD (KW) 110% for 1 hour, 125% for 10 minutes, 150% for 10

seconds

FREQUENCY 50Hz, 60Hz or 400Hz Fixed settings

47 - 500 Hz Variable

VOLTAGE THD < 1% max. Vthd at 50 or 60Hz

< 2% max. Vthd at 400Hz

LOAD REGULATION ±1% @ 50/60Hz, ±2% @ 400Hz with Automatic Gain

Control (AGC) enabled

LINE REGULATION ±1% maximum for ±10% line voltage change

LOAD TRANSIENT

RESPONSE AND

RECOVERY TIME

150 microseconds for 50% load step and 300

microseconds for 100% load step.

LOAD POWER

FACTOR Delivers full rated kVA into any Power Factor load.

LOAD BALANCE

RESTRICTION None. Each phase is independently regulated

ISOLATION An input transformer with an electrostatic shield

provides isolation between the input and output of the

system.

OVER CURRENT

PROTECTION

Integral electronic current limiting with auto

recovery. Output Circuit Breaker is optional.

AC Output Specifications

FREQUENCY Range

20 to 1000 Hz

Resolution

4 significant digits, e.g. 400.0

Accuracy

±0.01%,

VOLTAGE Range

0 to VMAX

Resolution

0.1 VAC steps.

Accuracy

±0.2% of range +cal.ref.

CURRENT LIMIT Range

0 to I

RMS

max

Resolution

±0.05%

Accuracy

±3%, FS

PROGRAMMABLE

OUTPUT IMPEDANCE

Dynamic output impedance (Zo) is programmable,

± Zo, MAX in 0.1% steps. Zo value in milliohms and

typically results in a ±10% change in output voltage at

maximum rated load current.

OPERATING TEMP Operating: 0º to +40ºC (32º to 104ºF) – Storage: -10º to

+70ºC (+14º to +158ºF)

RELATIVE HUMIDITY 0 to 95% non-condensing

NOISE LEVEL 65 dbA at 3 feet

EFFICIENCY 85 % typical at full load

COOLING/

VENTILATION

Self-Contained fans; bottom intake, top exhaust, 1200

CFM.

HEAT DISSIPATION AT

FULL LOAD

20 kBTU/HR (6 kW/HR)

SERVICE ACCESS Unit is designed for front access. Power Cabling is routed

through either top or bottom knock-outs.

CERTIFICATION CE, ETL (Optional)

ALTITUDE Operating 6000 Ft. Storage 40,000 Ft.

VOLTAGE

(True RMS)

Range

0-354V

L-N

, 0-708V

L-L

Resolution

0.1 VAC to front panel.

0.001 VAC to remote interface.

Accuracy

±0.2% of range +cal.ref.

CURRENT

(True RMS)

Range

4,000Apk

Resolution

0.01A to front panel.

0.001A to remote interface.

Accuracy

±0.2% of range +cal.ref.

POWER Measures True Power (kW), Apparent Power (kVA)

Power Factor and Crest Factor.
Range

1.4MW / 1.4MVA

Resolution

1.0 Watt

POWER/CREST

FACTOR

Calculated and displayed to three significant digits.

INPUT

VOLTAGE

208

VAC∆

±10%

240

VAC∆

±10%

380

VAC∆

±10%

400

VAC∆

±10%

416

VAC∆

±10%

480

VAC∆

±10%

RECOMMENDED

SERVICE CURRENT

175 A

RMS

175 A

RMS

100 A

RMS

100 A

RMS

100 A

RMS

80 A

RMS

INPUT FREQUENCY 47–63 Hz

POWER FACTOR 0.85 lagging typical

PROTECTION Input CB Standard. Slow Turn-On Circuit is provided to

limit inrush current

AC Power Source is protected against Overcurrent, Short

Circuit, and Overtemperature.

AUDIBLE & VISUAL

ALARMS

Alter operator to any conditions requiring attention.

HEIGHT 72" / 1829 mm

WIDTH 36" / 914 mm

DEPTH 30" / 762 mm

WEIGHT 1,557 lbs. / 715 kg

INSTALLATION

CLEARANCE

36" at front of cabinet for service,

12" top, 0" side and rear

/G GPIB Interface, SCPI Commands & IEEE488.2 (standard)

/S RS232 Interface. SCPI Commands, Baudrate up to 38.4

kBps. (Replaces GPIB, no cost option)

UPC-Studio Windows AC Power Source control Software (no cost

option)
UPC Test Manager License (cost option) required for

Avionics or IEC test options listed below:

ABD0100 License for Avionics Test Sequences according to norm

ABD0100.8.1. Requires UPC-Test Manager Option.

A350 License for Avionics Test Sequences according to norm

Airbus A350. Requires UPC-Test Manager Option.

DO160 License for Avionics Test Sequences according to norm

DO160 Version E - Requires UPC-Test Manager Option.

IEC-AC-4XX IEC 61000-4 AC Immunity Test Sequences. Includes 4-11,

4-14, 4-27, 4-28 and 4-34. Excludes 4-13 Option.

SCU/UPC32-413 IEC 61000-4-13 Inter Harmonic Generator. Required to

run 4-13 tests. Includes 4-13 software.

DRIVERS LabView

and LabWindows

drivers available

Transformer

Options

:

Consult factory for details.

/CE CE Mark. Includes Output Circuit Breaker (/OCB)

/CSTB Casters

/OCB

Output Circuit Breaker

/M99575

Split Phase Output Configurations (50 kw)

/M99583

Split Phase Output Configurations (32 kw)

Typical MS Options

Mechanical Specifications

General Specifications

Protection and Safety

Options for SCU/UPC32

Equipped MS Systems

Only

Parameter Settings

(with optional SCU/UPC32)

Measurements

(with optional SCU/UPC32)

Input Power Requirements

Advertising