Hpd series : product specifications, 300 w – Atec Sorensen-HPD Series User Manual

Page 3

Advertising
background image

858.458.0223

[email protected]

HPD Series : Product Specifications

1

Environmental

Operating Temperature

0 to 30°C for full rated output. Above 30°C, derate output linearly to zero at 70°C.

Storage Temperature

- 55 to 85°C

Humidity Range

0 to 80% RH, non-condensing

Physical

Dimensions

Width: 4.2” (109.2 mm)
Height: 5.2” (134.7 mm)
Depth: 11.7” (297 mm)

Weight

Approximately 7.7 lb (3.5 kg)

Input

Operational AC Input Voltage

Single unit: 104-127 Vac at 6 Arms; 47-63 Hz

General

Switching Frequency

100 kHz (nominal)

Voltage Mode Transient Response Time

< 500 μs recovery to 50 mV band for ±50% load change in the range of 25% to 100% of the rated load

Front Panel Voltage and Current Control

10-turn voltage and 1-turn current potentiometers (10-turn current optional)

Front Panel Voltage Control Resolution

0.02% of maximum voltage

AC Input Connector Type

EC 320 connector

Approvals

CE-marked units meet: EN61010-1, EN61000-6-2 and EN61000-6-4; CSA C/US certified to UL61010-1B and CSA C22.2 No 1010.1;
Meets USA EMC standard: FCC, part 15B, Class A; Meets Canadian EMC standard: ICES-001, Class A.

Analog Programming (with optional APG interface installed)

Remote On/Off and Interlock

2 to 25 Vdc high. <0.8 Vdc low. User-selectable.

Remote Analog Programming Option

0-10 Vdc for 0-100% of rated voltage or current ±1.0%, 0-10kΩ for 0-100% of rated voltage or current ±1.0%

Remote Monitoring

0-10 Vdc for 0-100% or rated voltage or current ±1.0%

Over Voltage Protection Trip Range

3 V to full output ±10%

Tracking Accuracy

±1% for series operation

300 W

109

Advertising