Asd series : product specifications, V1 asd acin option, V2 v3 option – Atec Sorensen_ASD Series User Manual

Page 3

Advertising
background image

858.458.0223

[email protected]

Model Number Description

ASD Series : Product Specifications

Physical

30 kW

20 kW

10 kW

Width

19.00in (48.3cm)

19.00in (48.3cm)

19.00in (48.3cm)

Depth

30.00” (76.2 cm)

30.00” (76.2 cm)

30.00” (76.2 cm)

Height

3U - 5.22” rack mount (13.25 cm)

3U - 5.22” rack mount (13.25 cm)

3U - 5.22” rack mount (13.25 cm)

Weight

≤125 lbs (56.69 kg)

Shipping Weight

Contact factory for more product & shipping weights

Mounting provisions

EIA rack-mount with slide provisions. Recommended rack slide: Jonathan slide, P/N 370EZ-28

AC Input Connector

Phoenix Contact terminal block

Protective Ground

1/4-20 stud

Output Connectors

bus bars with 3/8-16 inserted PEM nuts

Water Connections

3/8-18 NPTF hex bulkhead

Ambient Temperature

0 to 50ºC

Humidity

Relative humidity up to 95%, non-condensing

Advanced Digital Features (Requires Optional Digital Control):

Graphical User Interface

Graphical User Interface (Windows based) enables remote control and display of the supply operation including the a
dvanced features listed below:

Oscilloscope Function (125 Hz)

Up to two parameters; Voltage, current, output impedance, output cable impedance, output cable voltage drop, power delivered…

Data logging

Programmable update rate of 1 sec to 1000 sec (default 10 sec) with last 1000 points stored. Stored parameters include, output
voltage/current, programmed set points, input voltage, output impedance, cable impedance, total power deliver, power meter,
internal faults

System fault reporting

Outside of set point, output impedance (detection of cabling, connection or load problems)

10–320 kW

Water cooling specifications

Flow

1.5 gpm nominal, 1.25gpm minimum, 1.75gpm maximum. Internal condensation must be prevented by ensuring that the
temperature of the coolant is sufficiently high compared with the ambient air dew point

Temperature

25

ºC nominal, 20ºC minimum, 30ºC maximum

Maximum pressure

80 PSI

Pressure drop

typical 12 PSI @ 1.5gpm per chassis

Regulatory

Certified to UL/CSA 61010 and IEC/EN 61010-1 by a NRTL, CE Compliant, LVD Categories: Installation Category II: Pollution Degree 2; Class II Equipment: for Indoor Use Only.
Rack mount equipment requires proper enclosure provided in end use. EMC Directive, EN 61326:1998

-

V1

ASD

ACin Option

ACin (1 character) indicates the AC input voltage:
• D, for 380/400Vrms line to line, nominal voltage.
• E, for 480Vrms line to line, nominal voltage.

-

V2 V3

Option

Where V1, V2, V3 (2 characters)
indicate the individual module voltage levels:
• 40, for a 40V, 250A module.
• 60, for a 60V, 167A module.
• 00, for no module (empty slot).

Option (2 characters) indicates the optional interface type:
• 2A, Advanced digital feature package including full isolated analog
interface and Ethernet (Modbus-TCP) or RS485 interface.
• 2B, Advanced digital feature package including full isolated
analog interface and Ethernet (Industrial Protocol (IP)).
• 2G, Advanced digital feature package including full isolated analog
interface (SG-compatible) and Modbus-RTU (serial) inteface
• 1E, Advanced digital feature package including full isolated analog
interface and EtherCAT interface
• 1D, for SG-compatible isolated analog interface. No access to
advanced digital features or GUI. Serial port is available with
maintenance functions only.

Option (2 characters) indicates
other optional features:
• AA, standard unit AC Real-time clock
(must include advanced digital feature package).

3