Operating instructions – B&K Precision 1745A - Manual User Manual

Page 13

Advertising
background image

13

OPERATING INSTRUCTIONS

[email protected]

Figure 4. Typical Constant Voltage Operation.

c. If

an

earth

ground

reference

is

not

required,

the

configuration of Fig. 3Bmay be used. The scheme in Fig. 3C
should also be used where it is not known whether the
chassis is common with either the positive or negative
polarity.

d. If the chassis or common of the equipment being powered is

separate from both the positive and negative polarity power
inputs, use the connection shown in Fig. 3D.

5. Observe proper polarity. If the circuit being powered is not

equipped with reverse polarity protection, damage to the circuit can
result from reverse polarity. Use color coded hook-up leads, for
convenience in identifying polarity, red for (+) and black for (-).

6.Make sure that the hook-up leads offer sufficient current
capability and low resistance between the power supply and the
circuits being powered.

TYPICAL CONSTANT VOLTAGE OPERATION

1.

Before connecting the device to be powered to the power

supply, determine the maximum safe load current for the device
to be powered and set the current limit value (see “Setting
Current Limit” procedure in this section).
2.

Set Fine

VOLTAGE

control

to

center

and Coarse

VOLTAGE control to minimum (fully counterclockwise).

3.Turn off power supply and connect it to the device to be
powered (see “Hook-Up” procedure in this section).
8.

Turn on POWER switch. The CV indicator should light.

Advertising
This manual is related to the following products: