NOTE: Ball valves should be installed in
the condenser water supply and return lines
for unit isolation and water flow balancing.
All manual flow valves should be of the ball
valve design. Globe or gate valves should
not be used due to high pressure drops and
poor throttling characteristics.

Pressure

and

temperature

ports

are

recommended in condenser water supply
and return lines for system balancing. These
openings should be 5 to 10 pipe diameters
from the unit water connections. To allow
for mixing and temperature stabilization,
wells in the water piping should extend at
least ½ pipe diameter into the pipe.













Table 4 - Condenser Pressure Drops (Each Heat Exchanger)

SA-023

SA-028

SA-030

SA-035

GPM

PSI

GPM

PSI

GPM

PSI

GPM

PSI

45

4.2

45

4.2

45

4.2

45

1.7

39

3.3

39

3.3

39

3.3

39

35

2.8

35

2.8

35

2.8

35

SA-045

SA-050

SA-055

SA-058

GPM

PSI

GPM

PSI

GPM

PSI

GPM

PSI

45

4.2

45

4.2

45

4.2

45

4.2

39

3.3

39

3.3

39

3.3

39

3.3

35

2.8

35

2.8

35

2.8

35

2.8

SA-060

SA-065

SA-070

Heat Exchanger 1

Heat Exchanger 2

GPM

PSI

GPM

PSI

GPM

PSI

GPM

PSI

45

4.2

45

4.2

45

1.7

45

1.7

39

3.3

39

3.3

39

39

35

2.8

35

2.8

35

35



Each heat exchanger is equipped
with a refrigerant pressure relief
device to relieve pressure should
excessive

condensing

pressures

(>675 psig) occur. Codes may
require

installing

contractor

to

connect and route relief piping
outdoors.

The relief valve has a 5/8”

male flare outlet connection.

CAUTION



Installing contractor is responsible for
properly sizing and installing water
system components. Improper fluid
flow due to valves, piping, or
improper pump operation may result
in unacceptable unit operation and
void warranty.