43

Supply Fan Removal

1. Disconnect all electrical power sources

to the unit.

2. Disconnect the supply fans using the

quick connect electrical harness located
in the control compartment.

3. Remove the three screws on the hold

down bracket on the front side of the fan
assembly frame.

4. Remove the back fan access panel and

then remove the three screws on the rear
side of the fan assembly frame.

5. Slide the complete fan assembly forward

through the front supply fan access door.

Figure 18 - Back View with Supply Fan

Access Panel Removed


Figure 19 - Front View with Supply Fan

Access Door Open


Fan Airflow Adjustment
A specific air volume is delivered by the
fans with air volume bands in the blower
wheels or with VFDs. Field airflow
adjustment may be required at startup.

Air volume bands for the wheels are sized
according to the unit’s air delivery
specifications and can also be ordered from
the factory for field installation. Wheels
come standard with a 10% air volume band,
as a safety factor, in case additional air
volume is required from the unit.

Adjustment
If reduced air volume is required an air
volume band or larger air volume band can
be installed within the blower wheel to
reduce the amount of air delivered by the
wheel.

If the unit is factory equipped with the air
volume band and additional air volume is



Disconnect

all

electrical

power

sources before servicing the unit.
More than one power source may be
provided. Failure to do so may result
in injury or death from electrical
shock or entanglement in moving
parts.

WARNING

Hold Down

Bracket Screws

Hold Down

Bracket Screws