Table 3 - Freezing Points

% Glycol

Ethylene

Glycol

Propylene

Glycol

20 18°F 19°F
30 7°F 9°F
40 -7°F -6°F
50 -28°F

-27°F




















Piping systems should not exceed 10 ft/sec
velocity to ensure tube wall integrity and
reduce noise.

Table 4 - Coaxial Heat Exchanger Pressure Drops (WCC- & WHP-)

-002 -003 -004 -005

gpm psi gpm psi gpm psi gpm psi

3 1.9 6 2.3 8 3.3 7 1.6
5 4.3 8 3.7 10 4.8 11 2.8
7 7.4 10 5.3 12 6.7 15 4.6

-006 -008 -010 -013

gpm psi gpm psi gpm psi gpm psi

11 2.6 16 3.8 14 2 20 3.4
16 4.2 20 5.5 22 3.5 28 5.8
20 6.0 24 7.6 30 5.6 36 8.8

-016 -020 -025 -030

gpm psi gpm psi gpm psi gpm psi

28 3.6 28 2.3 40 3.9 56 4.1
36 5.3 44 3.9 56 6.6 72 6
44 7.8 60 6.1 72 10 88 8.9

-040 -050 -060

gpm psi gpm psi gpm psi

56 2.6 80 4.2 112 4.33

88 4.4 112 7.1 144 6.5

120 6.9 144 10.4 176 9.6









Do not exceed recommended
condenser fluid flow rates shown in
above table. Serious damage to or
erosion of the heat exchanger tubes
could occur.

CAUTION