AAON M2-036 User Manual

Page 67

Advertising
background image

67

2. Check for proper start-up and ignition as
outlined in Start-Up section.

3. Check the appearance of the burner flame.

4. Check that the circulating air fan is
operating and verify the proper airflow
through duct furnace.

5. Return thermostat or heat controller to
normal setting.







Troubleshooting

Table 11 - Problems, Causes and Solutions

Problem Possible

Cause

Solutions


Frosted evaporator coil, low
suction pressure


Restricted air flow
Low fan speed
Reversed blower rotation
Low refrigerant charge


Clean, or replace filters
Check fan drives
Correct wiring
Add refrigerant

Unit runs, but supplies warm air

Loss of refrigerant
Faulty expansion valve element
Plugged filter-drier

Check leaks, add refrigerant
Replace valve element
Replace filter-drier

Compressor starts, but opens
high pressure control

Refrigerant over-charged
Air in condenser coil
Condenser fan faulty
Condenser coil dirty

Remove some refrigerant
Evacuate and recharge refrigerant
Replace fan motor
Clean condenser coil

High suction pressure, but low
superheat

Oversized expansion valve
Poor sensing bulb location
Low superheat adjustment

Replace with correct expansion valve
Relocate sensing bulb, secure to suction line
Adjust expansion valve

Unit operates continuously

Low refrigerant charge
Unit undersized

Check and recharge to nameplate
Decrease load or resize unit
Thermostat set too low, increase temperature setting





















Advertising
This manual is related to the following products: