Caution – AAON M2-036 User Manual

Page 51

Advertising
background image

51

voltages from the average divided by the
average voltage.

Example:
(221V+230V+227V)/3 = 226V, then
100*(226V-221V)/226V = 2.2%, which
exceeds the allowable imbalance.

Check voltage imbalance at the unit
disconnect switch and at the compressor
terminal. Contact your local power company
for line voltage corrections.

Installing contractor must check for proper
motor rotation and check blower motor
amperage listed on the motor nameplate is
not exceeded. Motor overload protection
may be a function of the variable frequency
drive (VFD) and must not be bypassed.

Note: All units are factory wired for
208/230V, 460V, or 575V. If unit is to be
connected to a 208V supply, the transformer
must be rewired to 208V service. For 208V
service interchange the yellow and red
conductor on the low voltage control
transformer.
Red-Black for 208V
Yellow-Black for 230V














Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.

If any factory installed wiring must be
replaced, use a minimum 105°C type AWM
insulated conductors.

Thermostat Control Wiring
If a thermostat is used for unit control,
thermostat should be located on an inside
wall 4-5 feet above the floor where it will
not be subjected to drafts, sun exposure, or
heat from electrical fixtures of appliances.
Control wiring must deliver adequate
voltage to components to assure proper
operation. Control voltage returning from
controller circuit must be a minimum of 21
VAC. To assure proper wiring use the
following chart to determine the allowable
wiring distances.

Table 6 - Control Wiring

Wire Size (Stranded)
- Copper Conductors
Only

Total Wire Distance
Allowable

20 AWG

200 ft

18 AWG

350 ft

16 AWG

500 ft

14 AWG

750 ft

12 AWG

1250 ft


Total Wire Distance Allowable =
(Quantity of Control Wires) x
(Control Wire Distance)

Take the total wire distance allowable and
divide by the number of wires to be
connected. This indicates the distance
allowable for that size wire. The wiring to
the unit must not exceed the total wire
distance allowable. If the voltage at the
connectors is less than 21 VAC, isolation
relays must be installed. If under external
control 21 VAC must be field verified.


Rotation must be checked on all
MOTORS AND COMPRESSORS at
startup by a qualified service
technician. Scroll compressors are
directional and can be damaged if
rotated in the wrong direction.
Compressor rotation must be
checked using suction and discharge
gauges. Fan motor rotation should be
checked for proper operation.
Alterations should only be made at
the unit power connection

CAUTION

Advertising
This manual is related to the following products: