28

Figure 4 - Variable Capacity Compressor

Controller


Low Voltage Terminals
24COM

Module Common

24VAC

Module Power

C1 & C2

Demand Input

P1

Pressure Common

P2

Pressure Input

P3

Pressure Power 5VDC

P4

Pressure Shield

P5 & P6

Pressure Output

T1 & T2

Discharge Temperature Sensor




High Voltage Terminals
A1 & A2

Alarm Relay Out

M1 & M2

Contactor

L1

Control Voltage N

L2

Control Voltage L

U1 & U2

Digital Unloader Solenoid

V1 & V2

Vapor Injection Solenoid









The compressor controller modulates the
compressor unloader solenoid in an on/off
pattern according the capacity demand
signal of the system. The following table
shows the linear relationship between the
demand signal and compressor capacity
modulation. The compressor controller also
protects the compressor against high
discharge temperature. Refer to Table 7 for
the

relationship

between

thermistor

temperature readings and resistance values.

Table 6 - Demand Signal vs. Compressor Capacity Modulation




Demand

Signal (VDC)

Loaded %

Unloaded %

Time Loaded

Time

Unloaded

% Compressor

Capacity

1.00

Off

Off

Off

Off

0%

1.44

10%

90%

1.5 sec

13.5 sec

10%

3.00

50%

50%

7.5 sec

7.5 sec

50%

4.20

80%

20%

12 sec

3 sec

80%

5.00

100%

0%

15 sec

0 sec

100%


To avoid damaging the compressor
controller, DO NOT connect wires to
terminals C3, C4, T3, T4, T5, or T6.

WARNING