32

use of this product, the product must be able
to come in contact with the salts. These salts
may be beneath any soils, grease or dirt;
therefore, these barriers must be removed
prior to application of this product. As in all
surface preparation, the best work yields the
best results.

Apply CHLOR*RID DTS - Apply directly
onto the substrate. Sufficient product must
be applied uniformly across the substrate to
thoroughly wet out surface, with no areas
missed. This may be accomplished by use of
a pump-up sprayer or conventional spray
gun. The method does not matter, as long as
the entire area to be cleaned is wetted. After
the substrate has been thoroughly wetted,
the salts will be soluble and is now only
necessary to rinse them off.

Rinse - It is highly recommended that a hose
be used, as a pressure washer will damage
the fins. The water to be used for the rinse is
recommended to be of potable quality,
though a lesser quality of water may be used
if a small amount of CHLOR*RID DTS is
added.

Check

with

CHLOR*RID

International, Inc. for recommendations on
lesser quality rinse water.

DX Cooling
Set unit controls to cooling mode of
operation with supply fans on. Check
compressor operation, rotation, amperage
and voltage to the unit nameplate (check the

amperage on the load side of the compressor
contactor).
The scroll compressors are fully hermetic
and require no maintenance except for
keeping the shell clean.

Each refrigerant circuit includes a factory
provided liquid line filter drier. The unit
does not include a liquid line solenoid valve.
This must be field furnished and installed if
required by job conditions.

Condenser Fan Motor Lubrication
All original motors and bearings are
furnished with factory lubrication. They
require no lubrication.

Replacement Parts
Parts for AAON equipment may be obtained
from AAON, Inc. at www.aaonparts.com.
When ordering parts, reference the unit
serial number and part number.

AAON - Longview
Warranty, Service, and Parts Department
203 Gum Springs Rd.
Longview, TX 75602
Ph: 903-236-4403
Fax: 903-247-9219
www.aaon.com

Note: Before calling, technician should have
model and serial number of the unit
available

for

the

customer

service

department to help answer questions
regarding the unit.