Symptom

Resolution

Rate Pulse output does

not match data collection

system

1. Verify 0 Hz and MAX Hz flow settings
2. Place oscilloscope or frequency counter on the Rate Pulse module

outputs and verify frequency output

3. Run output TEST feature – verify that the Hz output coincides with

expected data collection system readings

4. Verify that “K-factor” has been calculated correctly:
K-factor = Hz/(flow/second)

Example:

Max Hz (2,500 Hz) = 10,000 Gallons/Minute

K-factor = 2,500 Hz / 166.7 Gallons/Second

K-factor = 15 pulses/gallon

5. Verify that the data collection system is accepting the pulses from the

DFX – connect to Turbine out or OUT/IN as required

DFX does not capture short

flow pulses

1. When run in AUTO mode, the DFX utilizes a series of filters that op-

timize readings for a particular flow range. The flow meter will take
several seconds to adjust to a step change in flow. To make the flow
meter respond quickly to changes in flow, decrease DAMPING, place
the meter into MANUAL AGC and lock the FILTER at NONE.