6. Troubleshooting

6 Troubleshooting

Before informing the fitter of a fault, make a note of the following
information:
- Type of gas used
- Boiler type
- Date of manufacture
- Year (01 = 2001, 02 = 2002, ...)
- Week
- Serial no. of the appliance

6.1 Error messages

Errors are signalled by the 4 lights on the control panel.

Light 1

Light 2

/

Light 3

/

Light 4

/

Flashing rapidly Flashing rapidly Flashing rapidly Flashing rapidly

Communication error :
Communication error
between the safety
control box and the PCB

Check the cable between the safety control box and
the PCB.
Press the Reset button for 2 seconds.
If the problem persists, contact the fitter.

Off

Off

Off

Off

The boiler does not
start up
: No current

Check the electrical connections.

Off

On

Off

Off

No flame detected
after 5 ignition
attempts

Press the Reset button for 2 seconds
If the problem persists, contact the fitter.

Flashing rapidly

On

Off

Off

Fault temperature
sensor heating outlet
:
The sensor circuit has
been broken or short
circuited

First check that the water is circulating in the boiler
(water pressure in the heating circuit, flow and return
valves open, valves and radiators open, etc.).
If the problem persists, contact the fitter.

Off

On

Flashing rapidly

Off

Domestic hot water
outlet sensor fault:
The
sensor circuit has been
broken or short circuited

First check that the water is circulating in the boiler
(water pressure in the heating circuit, flow and return
valves open, valves and radiators open, etc.).
If the problem persists, contact the fitter.

Off

Flashing rapidly

Off

Off

Thermostat activation:
Safety thermostat open

Check the fresh air inlet and flue gas discharge ducts
(or the forced flue).
Press the Reset button for 2 seconds.
If the problem persists, contact the fitter.

Off

On

Off

Flashing rapidly

WHE 2.24
Flue gas temperature
sensor error
:
- Insufficient draught
- The sensor circuit has

been broken or short
circuited

Check for adequate draw on the chimney
connection.
The boiler is in safety shutdown until the flue gas
temperature sensor is again operational. Wait 15
minutes.
If the problem persists, contact the fitter.

WHE 2.24 FF
Air pressure error
:
Insufficient draught

Check the fresh air inlet and flue gas discharge ducts
(or the forced flue).
Press the Reset button for 2 seconds.
If the problem persists, contact the fitter.

Off

On

Flashing rapidly Flashing rapidly

The water level and/or
pressure are too low

First check that the water is circulating in the boiler
(water pressure in the heating circuit, flow and return
valves open, valves and radiators open, etc.).
Top up the heating circuit with water.
Carry out a visual check for the presence of any
water leaks.