3 stopping the boiler, 4 commissioning the boiler, 1 commissioning – DE DIETRICH C 230 Eco User Manual

Page 11: 5 checking and maintenance, Precautions to take if there is a danger of frost, Commissioning, Checking and maintenance

Advertising
background image

11

20/02/09 - 300015144-001-C

C 230 ECO

4.3 Stopping the boiler

- Cut the power supply to the boiler.
- Close the gas valve.



Don't forget the risk of frost.

4.3.1

Precautions to take if there is a danger of frost

Heating circuit:
Use a correctly dosed antifreeze to prevent the heating water
freezing. If this cannot be done, drain the system completely. In all
cases, consult the fitter.

Domestic hot water circuit:
Drain the domestic water tank and pipes.

4.3.2

Precautions required in the case of long boiler stops (one or more years)

- Close the gas valve
- The boiler and the chimney must be swept carefully.

- Close the door of the boiler to prevent the internal circulation of air.

4.4 Commissioning the boiler



Initial commissioning must be done by a qualified
professional.

4.4.1

Commissioning

- Ensure that the boiler is switched off
- Remove the front casing
- Open the main gas valve
- Open the boiler control panel (Control panel instructions)
- Check the electrical connection
- Fill the installation with water and check hydraulic tightness (Pmin:

0.8 bar)

- Bleed the heating installation
- Fill the condensates siphon with water
- Check the connection of the combusted gas evacuation and the air

inlet

- Empty the gas inlet
- Open the gas valve on the gas pipe to the boiler
- Check the gas connection
- Turn the boiler on
- Turn the main switch to 8
- The boiler type is displayed on the screen for 5 seconds
- Provoke a heating request
- The boiler starts to operate
- Check the settings (See "Gas settings" - Installation and Service

Manual). If necessary, correct the settings

5 Checking and maintenance

The boiler is almost maintenance-free if it is set correctly. The boiler
only requires an annual check and cleaning if necessary.
Make the following checks at least 1 time a year:

- Checking the combustion in the boiler
- Setting the ignition electrode
- Checking tightness (hydraulics, combusted gas discharge and

gas)

- Checking the hydraulic pressure

Carry out the following maintenance at least 1 time a year:

- Clean the fan
- Clean the heat exchanger using the tool provided
- Clean the burner
- Clean the siphon.

Advertising