2 faults, Faults – DE DIETRICH C 230 Eco User Manual

Page 15

Advertising
background image

15

20/02/09 - 300015144-001-C

C 230 ECO

6.2.2

Faults

Faults

Code no.

Probable causes

Action

BOILER S.FAIL.

32

The boiler sensor is short circuited

- Reset the box
- Check the link and the connectors
- Replace the sensor if necessary

33

The boiler sensor is off

BACK S.FAILURE

6

The return sensor is short circuited

- Reset the box
- Check the link and the connectors
- Replace the sensor if necessary

7

The return sensor is off

8

The sensor reading is under -10°C

EXCHAN.S.FAIL.

2

The exchanger sensor is short circuited

- Reset the box
- Check the link and the connectors
- Replace the sensor if necessary

3

The exchanger sensor is off

4

The sensor reading is under -10°C

OUTSI. S.FAIL.

DHW S. FAILURE

AUX1.SENS.FAIL

AUX2.SENS.FAIL

UNIV.SENS.FAIL

OUTL S.A FAIL.

OUTL S.B FAIL.

OUTL S.C FAIL.

ROOM S.A FAIL.

ROOM S.B FAIL.

ROOM S.C FAIL.

SWIM.P.A S.FAIL

SWIM.P.B. S.FAIL

SWIM.P.C. S.FAIL

SOLAR S. FAIL

ST.TANK S.FAIL

DHW 2 S. FAIL

The corresponding sensor is off or short-
circuited.

Check the link and the connectors. Replace the sensor if
necessary.
See comments below.

BOILER 2 FAIL.

BOILER 3 FAIL.

BOILER 4 FAIL.

BOILER 5 FAIL.

BOILER 6 FAIL.

BOILER 7 FAIL.

BOILER 8 FAIL.

BOILER 9 FAIL.

BOILER 10 FAIL.

Error on a slave boiler, in a cascade
installation.

Press key

*

to see the error.

TA-S SHORT-CIR

The Titan Active System® is short-
circuited.

Check that the Titan Active System® is not short-
circuited.

TA-S DISCONNEC

The Titan Active System® is on an open
circuit.

Check that the Titan Active System® is correctly
connected.