Electrical connections

Pilot valve Type 6106

• Read the voltage, electrical power, type of protection and current from the rating plate!

• Voltage tolerance ±10 %;

• Ensure a long service life of the pilot valve by using a 10µ filter!

• Electrical connection: Instrument socket type 2506 to the tag connection on the coil (tigthening torque:

1 Nm);

• Proctection level IP 65 (only in combination with appliance socket type 2506);

• To match the cable run, the instrument socket can be mounted rotated by 180°.

NOTE

The coil heats up during opeation!

ATTENTION!

Media

• Filtered compressed air (max. particle size 10 µm), preferably non-oiled

• Operation is possible with oiled air

• Seal material:

NBR

• Perissible medium temperature:

max. + 50 ° C

• Perissible ambient temperature:

max. + 55 ° C

• Operational pressure range:

2 - 8 bar

ATTENTION!

NOTE

The pilot pressure of the pneumatic controller is dependent on the pressure of the flow
of medium: it must not exceed a maximum of 8 bar!

Observe the permissible pressure range given on the rating plate!
Pressure difference between Ports 1 and 3 ³ 2 bar
For temperatures below 0 °C, operation is limited to dry-air operation.

Take note of the voltage used; with alternating current, always
use the instrument socket Type 2506, or connect a rectifier into the circuit!
When screwing down the instrument socket onto the coil, ensure that the flat
seal is well seated!