Technical data Single valve
7.1.1. Temperature class T6
max. permissible surface temperature for T6: 85 °C
Temp.
class
Max. permis-
sible ambient
temperature
[°C]
Installation
Max. per-
missible
output [W]
Ignition
protec-
tion
type
Explo-
sion
group
T6
-40 ... +40
Block
installation
0,4
Ex ia
IIC
-40 ... +30
0,5
-40 ... +55
Single
valve
0,4
-40 ... +50
0,5
-40 ... +45
0,6
-40 ... +40
0,7
-40 ... +35
0,8
7.1.2. Temperature class T5:
max. permissible surface temperature for T5: 100 °C
Temp.
class
Max. permis-
sible ambient
temperature
[°C]
Installation
Max. per-
missible
output [W]
Ignition
protec-
tion
type
Explo-
sion
group
T5
-40 ... +55
Block
installation
0,4
Ex ia
IIC
-40 ... +45
0,5
-40 ... +40
0,6
-40 ... +35
0,7
-40 ... +25
0,8
-40 ... +70
Single
valve
0,4
-40 ... +65
0,5
-40 ... +60
0,6
-40 ... +55
0,7
-40 ... +50
0,8
-40 ... +45
0,9
-40 ... +40
1,0
-40 ... +35
1,1