Burkert Type 8611 User Manual
Page 24

24
ElectricalInstallation
terminal block 3
terminal Configuration external circuit
19
GND – Pt 100,
RTD
(0 ... 200 °C)
19
20
Pt 100
20
(
AIN3)
(+) Pt 100,
RTD (power
supply)
21
GND – Analog
input
21
A-GND
22
(
AIN1)
(+) Process
value input
4 - 20 mA /
0 - 10 V
22
21
4 - 20 mA / 0 - 10 V
(source)
A-GND
23
GND – Sensor,
actuating
element
23
GND
24
24 V DC
sensor supply
or actuating
element
24
23
24 V DC - Out (max. 1 A)
GND
terminal Configuration external circuit
25
Supply
of Type
8611
(
DIN3)
Frequency
input 2
(NPN or PNP)
Q
2
for ratio
control (
MODE
=
RATI)
Jumper 2
NPN
PNP
Trans-
mitter
12 or
24
24 V DC
GND
11 or
23
Clock
25
Supply of 8611
25
External
supply
(
DIN3)
Frequency
input 2
(NPN or PNP)
Q
2
for ratio
control
(
MODE =
RATI)
Jumper 2
NPN
PNP
Trans-
mitter
GND
11 or
23
GND
Supply
Clock
25
External supply
26
(
DIN2)
(+) Binary input
26
1, 11 or 23
0 ... 2,7 V
(log. 0)
3 ... 30 V
(log. 1)
max.
1 kHz
GND
english
Type 8611