Burkert Type 8686 User Manual

Page 22

Advertising
background image

22

Electricalinstallation

GND

24V

Top1

Bot1

Top2

Bot2

Fig. 15: Designation on PCB Type 8685

designation
on pcB

assignment

1)

24 V

Supply voltage +

24 V DC ±10%

GND

Supply voltage -

GND

Top 1

Top end position -
Top actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

Bot 1

Bottom end position -
Bot actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

Top 2

Top end position -
Top actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

Bot 2

Bottom end position -
Bot actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

Tab. 4: Connection for cable gland Type 8685

1)

Actuator assignment see “Fig. 16”.

Pilot air port

2 (P2)

Pilot air port
4 (P4)

Pilot air port
3 (P3)

Pilot air port

1 (P1)

actuator 1

(left)

actuator 2
(right)

Fig. 16: Pneumatic connection

→

Connect the wires (see pin assignment in “Tab. 4”).

note!

damage or malfunction due to ingress of dirt and moisture.

▶ To ensure degree of protection IP65 / IP67, tighten the union

nut of the cable gland according to the cable size you are using

(approx. 1.5 Nm).

→

Tighten the union nut of the cable gland on the body (approx. 1.5
Nm).

English

Type 8685 / 8686

Advertising