Electricalinstallation

9.2.2 electrical installation of control head

Type 8686

device connection for circular plug-in connector type 8686

→

Connect the circular plug-in connector of the control head as
described in “Tab. 5”.

6

1

7

5

4

3

2

8

Fig. 17: Assignment of circular plug (M12 x 1, 8-pole)

Use only straight connecting socket.

Pilot air port

2 (P2)

Pilot air port
4 (P4)

Pilot air port
3 (P3)

Pilot air port

1 (P1)

actuator 1

(left)

actuator 2
(right)

Fig. 18: Pneumatic connection

When the supply voltage is applied, the control head is operating.

→

Before the device can be used, the basic settings (see section
“10.3.1 Basic settings”) must still be made on the control head.

pin

wire
color

2)

assignment

3)

external circuit

1

white

Bottom end position -
Bot actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

1

2

brown

Top end position -
Top actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

2

3

green

Bottom end position -
Bot actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

3

4

yellow

Top end position -
Top actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

4

5

gray

Valve control Y2
Actuator 2 activated

high active, to activate
connect with 24 V

5

6

pink

Valve control Y1
Actuator 1 activated

high active, to activate
connect with 24 V

6

7

blue

Supply voltage –

GND

7

8

8

red

Supply voltage +

24 V DC ±10%

Tab. 5: Connection for circular plug-in connector Type 8686

2)

The indicated colors refer to the connecting cable available as an
accessory (919061).

3)

Actuator assignment see “Fig. 18”.