Electricalinstallation

device connection for cable gland type 8686

→

Use a cable cross-section of 0.25 mm² for the electrical connection.

Fastening

screws

M4 (2x)

Screw terminals

Cable holder

Fig. 19: Position of screw terminals Type 8686

→

Loosen the fastening screws M4 and pull the control head up
(only if the control head is already installed).

→

Install the cable gland, if necessary (approx. 1,5 Nm).

Valve1

GND

24V

Valve2

Top1

Bot1

Top2

Bot2

Fig. 20: Designation on PCB Type 8686

→

Guide the cables through the cable gland.

→

Connect the wires (see pin assignment in “Tab. 6”).

designation
on pcB

assignment

4)

external circuit

Bot2

Bottom end position -
Bot actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

Top2

Top end position -
Top actuator 2

24 V / 0 V (max. 0.1 A)

GND (7)

Bot1

Bottom end position -
Bot actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

Top1

Top end position -
Top actuator 1

24 V / 0 V (max. 0.1 A)

GND (7)

Valve2

Valve control Y2
Actuator 2 activated

high active, to activate
connect with 24 V

Valve1

Valve control Y1
Actuator 1 activated

high active, to activate
connect with 24 V

GND

Supply voltage -

GND

24V

Supply voltage +

24 V DC ±10%

Tab. 6: Connection for cable gland Type 8686

4)

Actuator assignment see “Fig. 18”.