Electricalinstallation24VDC

Output signals to the control center (e.g. PLC; for analog output option only)

Terminal Configuration

External circuit

2

3

Analogue position feedback +

Analogue position feedback GND

2

3

GND

+ (0/4 ... 20 mA)

Table 19:

Assignment of screw-type terminals - output signals to the control center - cable gland

Electrical supply voltage

Terminal Configuration

External circuit

6

7

Supply voltage +

Supply voltage GND

6

7

24 V DC ± 10 %
max. residual ripple 10 %

Table 20:

Assignment of screw-type terminals - Supply voltage - cable gland

Seal
body casing

Body casing

Figure 30:

Position of the seal in the body casing

→

Check that the seal is correctly positioned in the body casing.

NOTE!

Damage or malfunction due to penetration of dirt and humidity!

To ensure protection class IP65 / IP67:

• Tighten the union nut on the cable gland according to the cable size or dummy plugs used (approx. 1.5 Nm).

• Screw the body casing in all the way.

→

Tighten union nut on the cable gland (torque approx. 1.5 Nm).

→

Close the device (assembly tool: 674077

17)

).

When the power supply is applied, the positioner is operating.

→

Make the required basic settings and actuate the automatic adjustment of the positioner, as described in the
chapter entitled “12. Start-up”.

17)

The assembly tool (674077) is available from your Bürkert sales office.