Fault

Possible.cause

Remedy

SF LED lights up.

Wrong configuration.

→

Use the corresponding module from the
hardware catalogue.

Valve diagnosis trips (short circuit,
open outlet port).

→

Check the proper installation of the valve.

→

Replace defective valves.

→

Deactivate the diagnosis for valve posi-
tions not in use.

Module does not start due to
internal current limit (short circuits at
the outlet ports).

→

Remedy the short circuits (defective
valves at the outlet ports)

→

Carry out a voltage reset of the module /
system.

If an ET200iSP station has started once with Profibus address X, the address can be changed as follows:

→

Switch off the station.

→

Set the address 0 (all DIP switches in position OFF).

→

Switch on the station and wait approx. 10 seconds.

→

Switch off the station and wait approx. 10 seconds again.

→

Set the desired new address Y.

→

Switch on the station.

The new address is stored.

3.4.

Repair

If a repair is necessary, send the module to your local Bürkert subsidiary or contact our After-Sales Service.

Address and telephone number can be found in the chapter „General Information / Scope of Supply“.

Type 8650

english

Maintenance and Repair