TECHNICAL DATA
Operating voltage
24 V DC
Power consumption
max. 0,3 W (without proportional valve)
Output current (to valve)
max. 1,0 A
Operating temperature
- 10 ... + 60 °C
Interference resistance
to EN50082-2
Interference emission
to EN50081-2
Inputs
1 setpoint input
4 - 20 mA or 0 - 10 V, adjustable
1 actual value input
4 - 20 mA or 0 - 10 V, adjustable
Resolution for both inputs
10 Bit
Input impedance (4 - 20 mA)
< 200
Ω
Input impedance (0 - 10 V)
> 300 k
Ω
Output
PWM output
24 V pulse width modulated
Controller
Control algorithm
PI control
Scan time T
A
27 ms
Amplification factor K
P
0 - 10,00
Reset time T
N
0,05 - 200,1 s
Scaling of controlled variable
0,000 - 9999
Housing
Cable outlet
rotatable in 90° steps
System of protection
IP 65
Material
polyamide
Dimensions (W x H x D)
54 x 54 x 61 mm
Order no.
143 570