ERROR MESSAGES
Display
Cause
Remedy
ERR0
Standard signal at transmitter
Check standard signal of trans-
input lies outside range
mitter or its connection to controller
(4 - 20 mA, 0 - 10 V)
ERR1
Standard signal of external
Check standard signal
setpoint lies outside range
(4 - 20 mA, 0 - 10 V)
ERR2
Controller output to proportional
Increase the pressure in order to
valve is > 95%
reach the required setpoint with
the proportional valve selected
ERR9
Only in mode
SENS with
Set the lower limit for the valve drive
S LO
≥ S HI or
correctly value (see 6.6.9.
VALV)
EXLO
≥ EXHI
Set the lower limit for valve drive
correctly (see 6.6.9
VALV)
Actual value too great (can no
longer be compensated) or in
manual mode, the valve
cannot be closed