Wiring of the version with a single relay output – Burkert Type 8072 User Manual

Page 23

Advertising
background image

21

Installationandwiring

7.3.4. Wiring of the version with a single

relay output

Warning

shock hazard due to the voltage at the relay terminals, which
is higher than 48v.
• Before powering the device, always check that the connectors

are correctly plugged-in and tightened.

the device is not tight when the en 175301-803 fixed
connector is not wired:

→

Unscrew the nut [1] (see Fig. 10) on the 2508 female
connector supplied with the device.

→

Insert the plug with order code 444509, supplied with
the device, into the cable gland.

→

Screw the nut back.

→

Plug the sealed 2508 connector onto the
EN 175301-803 fixed connector.

1

2

3

1

2

3

1: Common

2: Relay, normally closed (NC)

3: Relay, normally open (NO)

4: Not connected

Fig. 19: Pin assignment on the EN 175301-803 fixed connector

1

2

4

3

5

1: V+ (12-36 V DC)
2: not connected
3: 0 V DC
4: not connected
5: Functional earth

The position of the 5-pin M12 fixed connector is adjustable:

→

Unscrew the locknut.

→

Turn the fixed connector to the desired position, by 360° max. to
prevent the cables from twisting inside the housing.

→

Tighten the locknut using a spanner, while keeping the fixed
connector in the desired position.

Fig. 20: Pin assignment of the 5-pin M12 fixed connector

pin of the m12 female cable
available as accessory
equipment (order code 438680)

colour of the wire (signal)

1

brown (V+)

2

not connected

3

blue (0 V DC)

4

not connected

5

grey (functional earth)

(1) Use a voltage limiter depending on the load selected, e.g. for the solenoid
valve, an EN 175301-803 connector with integrated varistor.
(*) Functional earth

English

installation and wiring